Special-PVC control cable adapted
to DIN VDE 0285-525-2-51 /
DIN EN 50525-2-51
Temperature range
flexing -15°C to +80°C
fixed installation -40°C to +80°C
Nominal voltage
U0/U 300/500 V
Test voltage
4000 V
Breakdown voltage
min. 8000 V
Insulation resistance
min. 20 MOhm x km
Minimum bending radius
flexing 7,5x cable Ø
fixed installation 4x cable Ø
Radiation resistance
up to 80x106 cJ/kg (up to 80 Mrad)
Bare copper conductor, to
DIN VDE 0295 cl.5, fine wire,
BS 6360 cl.5, IEC 60228 cl.5
Core insulation of special PVC
compound type Z 7225
Core identification to DIN VDE 0293
black cores with continuous white
numbering
GN-YE conductor, 3 cores and above
in the outer layer
Cores stranded in layers with
optimal lay length
Outer sheath of special PVC
compound type TM2 to
DIN VDE 0207-363-4-1 /
DIN EN 50363-4-1
Sheath colour: grey (RAL 7001)
With meter marking
G = with GN-YE conductor
x = without GN-YE conductor (OZ)
We supply any "desired length" of stranded
cores without outer sheath, core insulation
colour acc. RAL 9005 with number
combination acc. customers requirement.
Please note "cleanroom qualified"
when ordering.
AWG sizes are approximate equivalent
values. The actual cross section is in mm².
Screened analogue type:
F-CY-JZ,
F-CY-OZ (LiY-CY),
Y-CY-JB,
Y-CY-JZ
These cables are appropriate for flexible use with medium mechanical stresses, and free movement without tensile stress or forced movements in dry, moist and wet rooms but not open air. Suitable to be used as measuring and control cables in tool machines, conveyor belts, assembly lines, plant engineering, AC technology, steel production and other manufacturing environments. Selected PVC compounds guarantee good flexibility as well as an economic and fast installation.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.