Special-PVC control cable for
interlocking purposes adapted
to DIN VDE 0285-525-2-51 /
DIN EN 50525-2-51
Temperature range
flexing -15°C to +80°C
fixed installation -40°C to +80°C
Nominal voltage U0/U 300/500 V
Test voltage 4000 V
Breakdown voltage min. 8000 V
Insulation resistance
min. 20 MOhm x km
Minimum bending radius
flexing 7,5x cable Ø
fixed installation 4x cable Ø
Radiation resistance
up to 80x106 cJ/kg (up to 80 Mrad)
Bare copper conductor, to
DIN VDE 0295 cl.5, fine wire,
BS 6360 cl.5, IEC 60228 cl.5
Core insulation of special PVC
compound type Z 7225
Core identification to DIN VDE 0293
orange cores with continuous black
numbering
JZ-version with GN-YE conductor
3 cores and above
OZ-version without GN-YE conductor
Cores stranded in layers with
optimal lay length
Outer sheath of special PVC
compound type TM2 to
DIN VDE 0207-363-4-1/DIN EN 50363-4-1
Sheath colour: orange (RAL 2003)
With meter marking
G = with GN-YE conductor
x = without GN-YE conductor (OZ)
AWG sizes are approximate equivalent
values. The actual cross section is in mm².
These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air, as control cable acc. to EN 60204 part 1 and VDE 0113 part 1. As per recommendation of the specified standards the insulated conductors of control current circuits should be coloured orange, when they are used for interlocking purposes. These control circuits are supplied with an external power and remain active under current when the main switch is disconnected or switched off.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.