Special-PVC control cable adapted
to DIN VDE 0285-525-2-51/
DIN EN 50525-2-51
Temperature range
flexing -15°C to +80°C
fixed installation -40°C to +80°C
Nominal voltage U0/U 300/500 V
Test voltage 4000 V
Breakdown voltage min. 8000 V
Insulation resistance
min. 20 MOhm x km
Minimum bending radius
flexing 7,5x cable Ø
fixed installation 4x cable Ø
Radiation resistance
up to 80x106 cJ/kg (up to 80 Mrad)
Bare copper conductor, to
DIN VDE 0295 cl.5, fine wire,
BS 6360 cl.5, IEC 60228 cl.5
Core insulation of special PVC
compound type Z 7225
Core identification to DIN VDE 0293
black cores with continuous white
numbering
GN-YE conductor, 3 cores and above
in the outer layer
Cores stranded in layers with
optimal lay length
Outer sheath of special PVC
compound type TM2 to
DIN VDE 0207-363-4-1/DIN EN 50363-4-1
Sheath colour: black (RAL 9005)
With meter marking
G = with GN-YE conductor
x = without GN-YE conductor (OZ)
AWG sizes are approximate equivalent
values. The actual cross section is in mm².
Screened analogue type:
JZ-500-C black
These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms and in open air. Must not be laid directly in soil or water. When screened for measurement, control and control line etc. in mechanical and plant engineering, machine tools, production lines and conveyor belts.
CE = Product conforms with Low-Voltage Directive 2014/35/EU.